Backflow Prevention Test Report Example

Example document for Backflow Prevention Test Report. Use this as a reference when creating your own.

Professional Review Required

This document involves significant legal, financial, or compliance considerations. You must have a qualified professional review and approve this document before use. Do not rely on this template as legal advice.

Document: Backflow Prevention Test Report

Example Document

Last updated 7/29/2026

Backflow Prevention Test Report

1. Property Details

  • Property Owner/Company Name: Smith & Sons Pty Ltd
  • Property Address: 123 Industrial Ave, Auburn, NSW, 2144
  • Water Authority/Account Number: Sydney Water - 98765432
  • Test Date: 15/03/2024

2. Device Details

  • Device Location: Ground floor plant room, adjacent to main inlet
  • Device ID/Serial Number: BF-45892-X
  • Device Type: RPZD (Reduced Pressure Zone Device)
  • Size (mm): 50mm
  • Manufacturer: Watts
  • Model: 009
  • Year of Manufacture: 2019

3. Test Equipment Details

  • Tester Name: John Doe
  • Licence Number: NSW123456
  • Test Gauge Serial Number: G-2021-88
  • Gauge Calibration Due Date: 01/11/2024

4. Test Results (RPZD)

  • Inlet Pressure (kPa): 520
  • Zone Pressure (1st Check Closed) (kPa): 260
  • Relief Valve Opening Pressure (kPa): 170
  • Relief Valve Closing Pressure (kPa): 140
  • Check 1 (Shut-off) Pressure (kPa): 505
  • Check 2 (Shut-off) Pressure (kPa): 510

5. Test Results (DCV)

  • N/A

6. Outcome

  • Test Result: PASSED
  • Reason for Failure (if applicable): N/A
  • Repair Action Taken: N/A

7. Declaration I, the undersigned, certify that the above information is true and correct. I tested the device using a gauge that is currently calibrated. The test was conducted in accordance with AS/NZS 3500.1.

  • Plumber Signature: J. Doe

  • Date: 15/03/2024

  • Property Owner Acceptance: B. Smith

  • Date: 16/03/2024

Notes

This example shows a test for a 50mm RPZD at an industrial property. The Zone Pressure is roughly half the Inlet Pressure, which is expected. The Relief Valve opens at a suitable pressure difference. The Check valves hold pressure well. The gauge is within its calibration date. The result is a Pass.

About this Example

Part of the Backflow Prevention Test Report document collection

Document Type

Backflow Prevention Test Report

A record of inspection and testing results for a backflow prevention device to ensure it meets Australian Standards and local council requirements.

Complexity

moderate

Risk Level

high