Document: Electrical Test and Tag Log

Example Document

Last updated 7/30/2026

Electrical Test and Tag Log

Business Name: Smith's Building Services Pty Ltd ABN: 12 345 678 901 Address: 42 Builder Lane, Brunswick, VIC 3056 Person Responsible: Jane Smith Phone: 0400 123 456 Email: admin@smithbuilding.com.au

Equipment Register

Item IDAsset DescriptionSerial NumberLocation/DepartmentClass (Type)
TL-001Makita Cordless Drill405932Site ShedPortable Class I
TL-002240V Extension Lead 10mN/ASite ShedExtension Lead
TL-003Site Saw882100Workshop FloorPortable Class I

Test Records

Item IDTest DateNext Test DueTester NameTester SignatureVisual InspectionEarth ContinuityInsulation ResistancePolarityOverall ResultTag NumberAction TakenNotes
TL-00101/03/202301/06/2023Bob JonesB.JonesPassPassPassN/APassT-5521N/ABattery removed for test
TL-00201/03/202301/06/2023Bob JonesB.JonesPassPassPassPassPassT-5522N/APlug inspected OK
TL-00301/03/202301/06/2023Bob JonesB.JonesFailFailFailN/AFailN/ATagged out DESTROYCasing cracked guard broken

Failed Equipment Register

Item IDDate FailedDefect DetailsAction TakenDate Repaired/DisposedAuthorised By
TL-00301/03/2023Cracked casing and broken blade guard. Earth bond > 1 ohm.Destroyed via bin cut in half.02/03/2023Jane Smith

Competent Person Details

Name: Bob Jones Qualification: Licensed Electrician (Lic No. 99999) Tester ID Number: TE-882 Expiry Date: 01/01/2025

Notes

This example shows a typical scenario for a construction business. The 'Next Test Due' date is set for 3 months later which aligns with the hostile environment requirement of AS/NZS 3760. The failed item (TL-003) was clearly identified removed from service and destroyed with a record kept.

About this Example

Part of the Electrical Test and Tag Log document collection

Document Type

Electrical Test and Tag Log

A record used to track the inspection and testing of portable electrical appliances to ensure workplace safety compliance.

Complexity

moderate

Risk Level

high